Press Trade Fair Newsletter Sitemap Search:

Dimplex / Products / Heat pumps / Air-to-Water / Indoor installation

LI 9TU

High-efficiency air-to-water heat pump

LI 9TU
LI 9TU

The new high-efficiency heat pumps for indoor installation feature a flexible air circuit and a simple hydraulic connection. The outside air is drawn in at the back of the device. No air ducts are required. Thanks to the EC 3D radial fan, the air outlet can be on the left, right or top of the casing (as needed). The hydraulic connection of the heat pump can be perfectly adjusted to the given conditions. For installation, the flow and return can lead into the casing from the left or the right, as required.

The benefits at a glance:

  • Variable air outlet to the left, right or top with the
  • option of relocating the hydraulic connections from the right to the left
  • Electronic expansion valve for high seasonal performance factors and low operating costs
  • Free-swinging compressor baseplate and slow-running EC radial fan for low noise emissions
  • WPM EconPlus heat pump manager with integrated thermal energy metering and flow switch for high operational safety
  • Compact dimensions for space-saving installation - installation with built-under buffer tank PSP 120E possible

Information on leak tests and refrigerant quantities can be found here.

Seal of approval EHPA

European Heat Pump Association - EHPA
 

Technical data

High-efficiency air-to-water heat pump (Low temperature)
Order reference LI 9TU
Casing colourWhite (similar to RAL 9003)
Max. flow temperature60 °C
Lower operating limit heat source (heating operation) / Upper operating limit heat source (heating operation)-20 to 35 °C
Heat output with 1 compressor / COP A7/W35*5,4 kW / 3
Heat output 1 compressor / COP A2/W35*6,8 kW / 3,9
Heat output with 1 compressor / COP A7/W35*8,5 kW / 4,7
Heat output with 1 compressor / COP A10/W35*8,9 kW / 5
Nominal power consumption according to EN 14511 at A2/W351,7 kW
Sound power level device50 dB (A)
Sound pressure level in 1 m (indoors)43 dB (A)
Refrigerant / Amount of refrigerantR410A / 3,7 kg
Max. heating water flow rate / Pressure drop1,5 m³/h / 19300 Pa
Heat source flow (min.)3700 m³/h
Dimensions (W x H x D)**960 x 1560 x 780 mm
Weight256 kg
Connection voltage3/N/PE ~400 V, 50 Hz
Starting current with soft starter16 A
Fuse protectionC 10 A
Type of defrostingReverse circulation
Connection heating1 ¼ inch
Seal of approval EHPA (valid until)Yes / 12.12.2014

*Heat output and COP according to EN 14511 at A2/W35 (A2 = air intake temp. +2 °C, W35 = heating water outlet temp. +35 °C)

**Please note that additional space is required for pipe connections, operation and maintenance.