Press Trade Fair Newsletter Sitemap Search:

Dimplex / Products / Heat pumps / Air-to-Water / Outdoor installation

LA 16TAS

Air-to-water heat pump

LA ..TAS
LA ..TAS

Air-to-water heat pump for outdoor installation with external temperature controlled WPM 2006 plus heat pump manager. Sound-optimised through the use of low-noise 'owl's wings' ventilator blades. Energy-efficient defrosting by reverse circulation. High coefficients of performance (COP) thanks to compliance with EN 14511 for larger volume flows on the heat consumption side. Universal design with optional domestic hot water preparation and flexible expansion possibilities for:

  • Bivalent or bivalent-renewable operating mode
  • Distribution systems with unmixed and mixed heating circuits
The minimum clearances must be observed for installation close to walls. Integrated flow sensor and soft starter; return sensor and external temperature sensor included in the scope of supply.
The EVL ... electric cable for connecting the heat pump and the heat pump manager, must be ordered separately.

Information on leak tests and refrigerant quantities can be found here.

Seal of approval EHPA

European Heat Pump Association - EHPA
 

Technical data

Air-to-water heat pump (Low temperature)
Order reference LA 16TAS
Casing colourWhite aluminium (similar to RAL 9006)
Max. flow temperature58 °C
Lower operating limit heat source (heating operation) / Upper operating limit heat source (heating operation)-25 to 35 °C
Heat output with 1 compressor / COP A7/W35*10 kW / 2,7
Heat output 1 compressor / COP A2/W35*11,7 kW / 3,2
Heat output with 1 compressor / COP A7/W35*14,6 kW / 3,7
Heat output with 1 compressor / COP A10/W35*16,6 kW / 3,9
Nominal power consumption according to EN 14511 at A2/W353,7 kW
Sound power level device62 dB (A)
Sound pressure level in 10 m32 dB (A)
Refrigerant / Amount of refrigerantR404A / 3,5 kg
Max. heating water flow rate / Pressure drop2,6 m³/h / 11900 Pa
Heat source flow (min.)4000 m³/h
Dimensions (W x H x D)**1075 x 1550 x 852 mm
Weight231 kg
Connection voltage3/N/PE ~400 V, 50 Hz
Starting current with soft starter20 A
Fuse protectionC 13 A
Type of defrostingReverse circulation
Connection heating1 inch
Seal of approval EHPA (valid until)Yes / 08.11.2013

*Heat output and COP according to EN 14511 at A2/W35 (A2 = air intake temp. +2 °C, W35 = heating water outlet temp. +35 °C)

**Please note that additional space is required for pipe connections, operation and maintenance.

Product data sheet with system accessories: Data sheet as PDF Data sheet by e-mail

Instruction for use: Instruction for use as PDF

Product information: Product information as PDF

Equipment data: Equipment data as PDF

Declaration of conformity: Declaration of conformity as PDF

» Login