Press Trade Fair Newsletter Sitemap Search:

Dimplex / Products / Heat pumps / Air-to-Water / Outdoor installation

LA 35TUR+

Reversible air-to-water heat pump with two performance levels

LA 35TUR+
LA 35TUR+

The reversible air-to-water heat pump from Dimplex is an energy-efficient heating and cooling device. The integrated regulation enables heating in winter and cooling in summer with fan convectors and panel heating. In cooling operation, an integrated additional heat exchanger uses the waste heat directly as a free energy source for domestic hot water and swimming pool water preparation. Particularly high coefficients of performance (COPs) are obtained when the waste heat in cooling operation can be used continuously (e.g. for pre-heating a production process).

The benefits at a glance:

  • Maximum flow temperature in heating operation 56°C - Minimum flow temperature for cooling 9°C
  • External temperature operating limits for heating -25°C to 40°C, for cooling 10°C to 45°C
  • Naturally quiet operation through electronically controlled fan and thoroughly sound-proofed compressor housing
  • Regulation for combining fan convectors and silent cooling via floor, wall and ceiling surfaces with dew point monitoring
  • Integrated thermal energy meter

Information on leak tests and refrigerant quantities can be found here.

Technical data

Reversible air-to-water heat pump with two performance levels (Low temperature)
Order reference LA 35TUR+
Casing colourWhite aluminium (similar to RAL 9006)
Max. flow temperature60 °C
Lower operating limit heat source (heating operation) / Upper operating limit heat source (heating operation)-25 to 40 °C
Lower operating limit heat source (cooling operation) / Upper operating limit heat source (cooling operation)10 to 45 °C
Standard temperature spread heating EN 145115,0 K
Heat output with 1 compressor / COP A7/W35*9,9 kW / 2,9
Heat output with 2 compressor / COP A7/W35*17,6 kW / 2,8
Heat output 1 compressor / COP A2/W35*13,6 kW / 4
Heat output 2 compressors at A2/W35 / COP A2/W35*23,6 kW / 3,7
Heat output with 1 compressor / COP A7/W35*17,3 kW / 4,8
Heat output with 2 compressor / COP A7/W35*30,2 kW / 4,5
Standard temperature spread cooling EN 145115 K
Cooling capacity 1 compressor / COP A35/W7*13,6 kW / 3,3
Cooling capacity 2 compressor / COP A35/W18*29,7 kW / 3,1
Nominal power consumption according to EN 14511 at A2/W356,21 kW
Sound power level device72 dB (A)
Sound pressure level in 10 m43 dB (A)
Refrigerant / Amount of refrigerantR417A / 22 kg
Heat source flow (min.)5000 m³/h
Max. heating water flow rate / Pressure drop5,2 m³/h / 2900 Pa
Dimensions (W x H x D)**1735 x 2100 x 980 mm
Weight595 kg
Connection voltage3/N/PE ~400 V, 50 Hz
Starting current with soft starter30 A
Fuse protectionC 25 A
Type of defrostingReverse circulation
Connection heating1 ½ inch

*Heat output and COP according to EN 14511 at A2/W35 (A2 = air intake temp. +2 °C, W35 = heating water outlet temp. +35 °C)

**Please note that additional space is required for pipe connections, operation and maintenance.

Product data sheet with system accessories: Data sheet as PDF Data sheet by e-mail

Instruction for use: Instruction for use as PDF

Product information: Product information as PDF

Equipment data: Equipment data as PDF

Declaration of conformity: Declaration of conformity as PDF