LA 60TU

Heat pump for heating purposes for outdoor installation, with wall-mounted WPM EconPlus heat pump manager and two compressors for output reduction when operating at partial load. Sound-optimised through the use of two slow-running EC-3D fans, an encapsulated compressor housing and a free-swinging compressor baseplate for solid-borne sound insulation. High coefficients of performance (COP) through high-performance evaporator, electronic expansion valve and compliance with the requirements of EN 14511 for larger volume flows on the heat consumption side. High operational safety through sensor monitoring of the refrigeration circuit for energy-efficient defrosting; integrated thermal energy metering (display of the thermal energy volume for heating and domestic hot water preparation on the WPM EconPlus heat pump manager). Access for service work on the outlet side; the minimum clearances must be observed for installation close to walls. Can be easily transported with a lift truck (accessible from underneath) or lifting lugs. Universal design with two compressors for modulating operation, optional domestic hot water preparation and flexible expansion options for:

  • Bivalent or bivalent-renewable operating mode
  • Distribution systems with unmixed and mixed heating circuits
At an external temperature of -10 °C, the maximum flow temperature that can be achieved is 60 °C. Soft starter, integrated flow and return sensors; external sensor (standard NTC-2) included in the scope of supply. Electrical connection cable EVL ..UE between heat pump and heat pump manager must be ordered separately.

Information on leak tests and refrigerant quantities can be found here.

Technical data

High-efficiency air-to-water heat pump with two performance levels (Medium temperature)
Order reference LA 60TU
Casing colourWhite aluminium (similar to RAL 9006)
Max. flow temperature65 °C
Lower operating limit heat source (heating operation) / Upper operating limit heat source (heating operation)-20 to 35 °C
Heat output with 1 compressor / COP A7/W35*21,2 kW / 3
Heat output with 2 compressor / COP A7/W35*39,2 kW / 2,9
Heat output 1 compressor / COP A2/W35*26,4 kW / 3,7
Heat output 2 compressors at A2/W35 / COP A2/W35*50 kW / 3,6
Heat output with 1 compressor / COP A7/W35*31,9 kW / 4,3
Heat output with 2 compressor / COP A7/W35*60,1 kW / 4,1
Heat output with 1 compressor / COP A10/W35*33,6 kW / 4,4
Heat output with 2 compressor / COP A10/W35*64,6 kW / 4,2
Nominal power consumption according to EN 14511 at A2/W3514,9 kW
Sound power level device74 dB (A)
Sound pressure level in 10 m50 dB (A)
Refrigerant / Amount of refrigerantR417A / 19,4 kg
Max. heating water flow rate / Pressure drop10,4 m³/h / 7200 Pa
Heat source flow (min.)14000 m³/h
Dimensions (W x H x D)**1900 x 2300 x 1000 mm
Weight915 kg
Connection voltage3/N/PE ~400 V, 50 Hz
Starting current with soft starter78 A
Fuse protectionC 50 A
Type of defrostingReverse circulation
Connection heating2 inch

*Heat output and COP according to EN 14511 at A2/W35 (A2 = air intake temp. +2 °C, W35 = heating water outlet temp. +35 °C)

**Please note that additional space is required for pipe connections, operation and maintenance.

Product data sheet with system accessories: Data sheet as PDF Data sheet by e-mail

Instruction for use: Instruction for use as PDF

Product information: Product information as PDF

Equipment data: Equipment data as PDF

Declaration of conformity: Declaration of conformity as PDF

» Login