Dimplex / Products / Heat pumps / Air-to-Water / Outdoor installation

LA 60TUR+

Reversible air-to-water heat pump.

LA 60TUR+
LA 60TUR+
  SG Ready

Heat pump for heating and cooling purposes for outdoor installation with wall-mounted heat pump manager and two compressors for output control in partial load operation. Sound-optimised by electronically controlled fans and an encapsulated compressor housing with free-swinging compressor baseplate for solid-borne sound insulation. High coefficients of performance (COP) through high-performance evaporator and compliance with the requirements of EN 14511 for larger volume flows on the heat consumption side. Optimised heating and cooling operation via an external four-way reversing valve which is activated by the controller (special accessory). High operational safety through sensor monitoring of the refrigeration circuit for energy-efficient defrosting; integrated thermal energy metering (display of the thermal energy volume for heating and domestic hot water preparation on the WPM EconR-E heat pump manager). Reversible refrigeration circuit with additional heat exchanger for higher domestic hot water temperatures in heating operation and waste heat recovery in cooling operation. Access for service work on the outlet side; the minimum clearances must be observed for installation close to walls. Can be easily transported with a lift truck (accessible from underneath) or lifting lugs. Universal design with flexible expansion options for:

  • Bivalent or bivalent-renewable operating mode
  • Combined distribution systems for heating and cooling
  • Unmixed and mixed heating and cooling circuit
At an external temperature of -10 °C, the maximum flow temperature that can be achieved is 55 °C. Silent cooling via panel heating/cooling systems requires the use of the room climate station (special accessory) to regulate the flow temperature on the basis of the air temperature and humidity of a reference room. Flow and return sensor integrated; external sensor (standard NTC-2) in the scope of supply. Dirt trap included with LA 35TUR+; LA 60TUR+ with built-in flow rate switch and dirt trap. Electrical connection cable EVL ..UE between heat pump and heat pump manager must be ordered separately. When installing an optional residual-current circuit-breaker, an RCD type B must be used, which detects AC and pulsating DC residual currents, as well as smooth DC residual currents.

 

Technical data

Reversible air-to-water heat pump.
Order reference LA 60TUR+
Heat pump code5006
Casing colourWhite aluminium (similar to RAL 9006)
Max. flow temperature60 °C
Lower operating limit heat source (heating operation) / Upper operating limit heat source (heating operation)-20 to 40 °C
Lower operating limit heat source (cooling operation) / Upper operating limit heat source (cooling operation)10 to 45 °C
Standard temperature spread heating EN 145115 K
Heat output A-7/W35 / COP A-7/W35*20,4 kW / 2,8
Heat output max. A-7/W35 / COP A-7/W35*39,7 kW / 3,00
Heat output A2/W35 / COP A2/W35*26,4 kW / 3,5
Heat output max. A2/W35 / COP A2/W35*47,6 kW / 3,4
Heat output A7/W35 / COP A7/W35*34,1 kW / 4,2
Heat output max. A7/W35 / COP A7/W35*55,3 kW / 3,8
Standard temperature spread cooling EN 145115 K
Cooling capacity 1 compressor / EER A35/W7*24,0 kW / 2,4
Cooling capacity 2 compressor / EER A35/W18 (2 compressors)*65,8 kW / 2,8
Nominal power consumption according to EN 14511 at A2/W3514,2 kW
Nominal power consumption according to EN 14511 at A7/W3514,95 kW
Sound power level74 dB (A)
Sound pressure level in 10 m45 dB (A)
Refrigerant / Amount of refrigerantR417A / 31 kg
Heat source flow (min.)10000 m³/h
Max. heating water flow rate / Pressure drop10,5 m³/h / 16100 Pa
Dimensions (W x H x D)**1900 x 2300 x 1000 mm
Weight966 kg
Rated voltage3/N/PE ~400 V, 50 Hz
Starting current78 A
Fuse protection***C 50 A
Type of defrostingReverse circulation
Connection heating2 inch

*Heating, cooling capacity and coefficients of performance (COP/EER) according to EN 14511

**Please note that additional space is required for pipe connections, operation and maintenance.

***Die Absicherung ist als allpolige Trennvorrichtung auszuführen (gemeinsame Abschaltung aller Phasen)!

Documents and downloads

Data sheetProduct data sheet with system accessories» via e-mail
Instruction for useInstruction for use» via e-mail
Operating instructions for users for the heat pump managerOperating instructions for users for the heat pump manager» via e-mail
Installation guide for Heat Pump ManagerInstallation guide for Heat Pump Manager» via e-mail
Operating instructions for installers for the heat pump managerOperating instructions for installers for the heat pump manager» via e-mail
Product informationProduct information» via e-mail
Equipment dataEquipment data» via e-mail
Foundation planningFoundation planning» via e-mail
Declaration of conformityDeclaration of conformity» via e-mail
» Login