Press Trade Fair Newsletter Sitemap Search:

Dimplex / Products / Heat pumps / Air-to-Water / Outdoor installation

LA 8PMS

Medium temperature air-to-water heat pump

Medium temperature air-to-water heat pump for outdoor installation with external temperature controlled WPM 2006 plus heat pump manager. Sound-optimised through the use of noise-reducing crescent wing axial fans and air deflector hoods; energy-efficient hot gas defrosting for optimum operation in combination with radiators. Universal design with optional domestic hot water preparation and flexible expansion possibilities for:

  • Bivalent or bivalent-renewable operating mode
  • Distribution systems with unmixed and mixed heating circuits
Integrated flow sensor and soft starter; return sensor and external temperature sensor included in the scope of supply.
The EVL ... electric cable for connecting the heat pump and the hydraulic tower must be ordered separately.

Information on leak tests and refrigerant quantities can be found here.

Technical data

Medium temperature air-to-water heat pump (Medium temperature)
Order reference LA 8PMS
Casing colourWhite aluminium (similar to RAL 9006)
Max. flow temperature65 °C
Lower operating limit heat source (heating operation) / Upper operating limit heat source (heating operation)-25 to 35 °C
Heat output with 1 compressor / COP A7/W35*4,5 kW / 2,5
Heat output 1 compressor / COP A2/W35*6 kW / 3,1
Heat output with 1 compressor / COP A7/W35*8 kW / 3,8
Heat output with 1 compressor / COP A10/W35*8,9 kW / 4,2
Nominal power consumption according to EN 14511 at A2/W352 kW
Sound power level device63 dB (A)
Sound pressure level in 10 m32 dB (A)
Refrigerant / Amount of refrigerantR290 / 1 kg
Max. heating water flow rate / Pressure drop1,5 m³/h / 7800 Pa
Heat source flow (min.)3500 m³/h
Dimensions (W x H x D)**1362 x 1361 x 852 mm
Weight232 kg
Connection voltage1/N/PE ~230 V, 50 Hz
Starting current with soft starter30 A
Fuse protectionC 20 A
Type of defrostingHot gas
Connection heating1 ¼ inch

*Heat output and COP according to EN 14511 at A2/W35 (A2 = air intake temp. +2 °C, W35 = heating water outlet temp. +35 °C)

**Please note that additional space is required for pipe connections, operation and maintenance.

Product data sheet with system accessories: Data sheet as PDF Data sheet by e-mail

Instruction for use: Instruction for use as PDF

Product information: Product information as PDF

Equipment data: Equipment data as PDF

Declaration of conformity: Declaration of conformity as PDF

» Login