Press Sitemap

Dimplex / Products / Heat pumps / Brine-to-Water / Heating and cooling

SI 50TUR

Reversible brine-to-water heat pump for indoor installation.

SI 50TUR
SI 50TUR
  SG Ready

Heat pump for heating and cooling with integrated regulation installed indoors. Variable connection options for brine and heating connections on the back board of the casing. A sound-optimised metal casing and the integrated solid-borne sound insulation with free-swinging compressor base plate make direct connection with the heating system possible. High coefficients of performance (COP) through electronic expansion valve and electronic pump control depending on the temperature spread in the brine and generator circuit. Optimised heating and cooling operation via an internal hydraulic four-way reversing valve which is activated by the controller. Sensor monitoring of the refrigeration circuit for a high degree of operational safety and integrated thermal energy metering (display of the calculated quantity of thermal energy for heating, domestic hot water and swimming pool water preparation). FWO function for more efficient domestic hot water preparation with increased domestic hot water temperatures and volumes of water to be drawn through optimised tank charging.
Universal design with two compressors for output regulation when operating at partial load, optional domestic hot water preparation and flexible expansion options for:

  • Bivalent or bivalent-renewable operating mode
  • Distribution systems with unmixed and mixed heating circuits
  • Use of load-variable tariffs (SG Ready)
Soft starter, flow and return sensors for the brine and heating circuit integrated. Dirt trap for brine circuit, external sensor (standard NTC-2), circulating pumps for brine and heat generator circuit in the scope of supply (observe the free compression). Brine package SZB must be ordered separately. (Spectrum of efficiency classes A+++ to D)

Seal of approval EHPA

European Heat Pump Association - EHPA
 
 

Technical data

Reversible brine-to-water heat pump for indoor installation.
Order reference SI 50TUR
Heat pump code6009
Max. flow temperature62 °C
Lower operating limit heat source (heating operation) / Upper operating limit heat source (heating operation)-5 to 25 °C
Lower operating limit heat source (cooling operation) / Upper operating limit heat source (cooling operation)10 to 30 °C
Standard temperature spread heating EN 145115 K
Heat output B0/W35 / COP B0/W35*25,1 kW / 4,9
Heat output max. B0/W35 / COP B0/W3548,4 kW / 4,5
Heat output B0/W55 / COP B0/W5522,1 kW / 2,90
Heat output max. B0/W55 / COP B0/W5543,2 kW / 2,7
Cooling capacity B20/W18 / EER B20/W1826,1 kW / 6,6
Cooling capacity 2 compressor / EER B20/W18 (2 compressors)60,1 kW / 6,2
Nominal power consumption according to EN 14511 at B0/W3510,8 kW
Sound power level61 dB (A)
Refrigerant / Amount of refrigerantR410A / 8,7 kg
Heat source flow (min.)9,3 m³/h
Max. heating water flow rate / Pressure drop8,4 m³/h / 5000 Pa
Dimensions (W x H x D)**1000 x 1665 x 805 mm
Weight490 kg
Rated voltage3/PE ~400 V, 50 Hz
Starting current49 A
Fuse protection***C 40 A
Connection heating2 ½ inch
Heat source connection2 ½ inch
Seal of approval EHPA (valid until)Yes / 23.11.2022

**Please note that additional space is required for pipe connections, operation and maintenance.

***Die Absicherung ist als allpolige Trennvorrichtung auszuführen (gemeinsame Abschaltung aller Phasen)!

Documents and downloads

Data sheetProduct data sheet with system accessories» via e-mail
Electrical documentation heat pumpElectrical documentation heat pump» via e-mail
Equipment dataEquipment data» via e-mail
Declaration of conformityDeclaration of conformity» via e-mail
» Login