Press Trade Fair Newsletter Sitemap Search:

Dimplex / Products / Heat pumps / Brine-to-Water / Universal for customer-specific versions

SI 50TE

Brine-to-water heat pump with two performance levels

SI 50TE
SI 50TE

Heat pump for heating purposes for indoor installation with integrated WPM 2007 plus controller. The control panel is integrated into a brown-red design screen and can also be used as wired remote control using the wall mounting set (special accessories MS PGD). Variable connection options for brine and heating connections on the back board of the casing. Access for service work from the front, no minimum clearance required on the sides, accessible from underneath with a lift truck. A sound-optimised insulated metal casing and the integrated solid-borne sound insulation with free-swinging compressor base plate make direct connection with the heating system possible. High coefficients of performance (COP) with economiser and compliance with the requirements of EN 14511 for larger volume flows on the heat consumption side. Universal design with optional domestic hot water preparation and flexible expansion possibilities for:

  • Bivalent or bivalent-renewable operating mode
  • Distribution systems with unmixed and mixed heating circuits
Integrated soft starter and load contactor for brine circulating pump, integrated flow and return sensors; external sensor (standard NTC-2) and dirt filter for brine circuit included in the scope of supply. Brine package must be ordered separately.

Information on leak tests and refrigerant quantities can be found here.

Seal of approval EHPA

European Heat Pump Association - EHPA
 

Technical data

Brine-to-water heat pump with two performance levels (Low temperature)
Order reference SI 50TE
Casing colourWhite (similar to RAL 9003)
Max. flow temperature58 °C
Lower operating limit heat source (heating operation) / Upper operating limit heat source (heating operation)-5 to 25 °C
Heat output 1 compressor at B5/W35 / COP at B0/W35*23,2 kW / 4,3
Heat output 2 compressors at B0/W35 / COP at B0/W3545,8 kW / 4,3
Heat output with 1 compressor / COP at B0/W4524,6 kW / 3,2
Heat output with 2 compressor / COP at B0/W4543,4 kW / 3,3
Nominal power consumption according to EN 14511 at B0/W3510,6 kW
Sound power level device57 dB (A)
Refrigerant / Amount of refrigerantR404A / 8,6 kg
Max. heating water flow rate / Pressure drop7,8 m³/h / 6400 Pa
Heat source flow (min.)11,1 m³/h
Dimensions (W x H x D)**1350 x 1890 x 775 mm
Weight486 kg
Connection voltage3/N/PE ~400 V, 50 Hz
Starting current with soft starter56 A
Fuse protectionC 50 A
Connection heating1 ½ inch
Heat source connection2 ½ inch
Seal of approval EHPA (valid until)Yes / 08.11.2013

*Heat output and coefficient of performance (COP) according to EN 14511 at B0/W35 (B0 = brine inlet temp. 0 ℃, W35 = heating water outlet temp. +35 °C)

**Please note that additional space is required for pipe connections, operation and maintenance.

Product data sheet with system accessories: Data sheet as PDF Data sheet by e-mail

Instruction for use: Instruction for use as PDF

Equipment data: Equipment data as PDF

Declaration of conformity: Declaration of conformity as PDF

» Login