Dimplex / Products / Heat pumps / Water-to-Water /
|
WI 100TU |
Water-to-water heat pump for indoor installation with integrated WPM EconPlus regulation and two compressors for output reduction when operating at partial load. The control panel is integrated into a brown-red design screen and can also be used as wired remote control using the wall mounting set (special accessories MS PGD). Variable connection options for the water and heating connections on the rear wall of the casing. Access for service work from the front, no minimum clearance required on the sides, accessible from underneath with a lift truck. Sound-optimised through insulated metal casing and double vibration-isolated compressor. Integrated solid-borne sound insulation for direct connection to the heating system. High coefficients of performance (COP) thanks to economiser, electronic expansion valve and compliance with the requirements of EN 14511 for larger volume flows on the heat consumption side. Sensor monitoring of the refrigeration circuit for a high degree of operational safety and integrated thermal energy metering (display of the calculated quantity of thermal energy for heating and domestic hot water preparation on the WPM EconPlus heat pump manager). Universal design with flexible expansion options for:
Information on leak tests and refrigerant quantities can be found here.
| High-efficiency water-to-water heat pump (Low temperature) | ||
|---|---|---|
| Order reference | WI 100TU | |
| Casing colour | White (similar to RAL 9003) | |
| Max. flow temperature | 58 °C | |
| Lower operating limit heat source (heating operation) / Upper operating limit heat source (heating operation) | 7 to 25 °C | |
| Heat output 1 compressor at W10/W35 / COP W10/W35 | 51,7 kW / 5,8 | |
| Heat output 2 compressors at W10/W35 / COP W10/W35 | 95,5 kW / 5,3 | |
| Heat output with 1 compressor / COP W10/W45 | 47,6 kW / 4,3 | |
| Heat output with 2 compressor / COP W10/W45 | 90,9 kW / 4,1 | |
| Nominal power consumption according to EN 14511 at W10/W35 | 18 kW | |
| Sound power level device | 70 dB (A) | |
| Refrigerant / Amount of refrigerant | R404A / 15,8 kg | |
| Max. heating water flow rate / Pressure drop | 16,5 m³/h / 17700 Pa | |
| Heat source flow (min.) | 21,2 m³/h | |
| Dimensions (W x H x D)** | 1350 x 1890 x 775 mm | |
| Weight | 593 kg | |
| Connection voltage | 3/N/PE ~400 V, 50 Hz | |
| Starting current with soft starter | 100 A | |
| Fuse protection | C 63 A | |
| Connection heating | 2 inch | |
| Heat source connection | 2 ½ inch | |
*Heat output and coefficient of performance (COP) according to EN 14511 at W10/W35 (W10 = ground water inlet temp. +10 °C, W35 = heating water outlet temp. +35 °C)
**Please note that additional space is required for pipe connections, operation and maintenance.