Press Trade Fair Newsletter Sitemap Search:

Dimplex / Products / Heat pumps / Air-to-Water / Indoor installation

LIK 8ME

Compact air-to-water heat pump with 90° air deflection

LIK 8ME
LIK 8ME

Heat pump for indoor installation with integrated regulation WPM 2007 plus. The control panel is integrated into a brown-red design screen and can also be used as wired remote control using the wall mounting set (special accessories MS PGD). The integrated air flow with 90° air deflection enables direct corner installation without air ducts or wall installation with air ducts on the air outlet side. Sound-optimised through low-noise axial-flow fan and vibration-isolated compressor. High coefficients of performance using an evaporator optimised for heating operation and energy-efficient defrosting by reverse circulation. Compact design with optional domestic hot water preparation and integrated components for direct connection of an unmixed heating circuit (must not be used for bivalent systems):

  • Expansion vessel (24 l)
  • Heat circulating pump (free compression 45,000 Pa)
  • Overflow valve and safety module
  • Buffer tank (50 l) with integrated 2 kW heating element
Integrated soft starter, flow and return-flow sensors; external sensor (standard NTC-2) and 3 flexible connecting hoses (1", 500mm) included in the scope of supply.

Information on leak tests and refrigerant quantities can be found here.

Technical data

Compact air-to-water heat pump with 90° air deflection (Low temperature)
Order reference LIK 8ME
Casing colourwhite
max. flow temperature58 °C
Lower operating limit heat source (heating operation) / Upper operating limit heat source (heating operation)-25 to 35 °C
Heat output with 1 compressor / COP A-7/W35*5,5 kW / 2,6
Heat output 1 compressor at A2/W35 / COP A2/W35*7,4 kW / 3,2
Heat output with 1 compressor / COP A7/W35*9,2 kW / 3,8
Heat output with 1 compressor / COP A10/W35*9,7 kW / 4
Nominal consumption according to EN 14511 at A2/W352,33 kW
Sound power level device53 dB (A)
Sound pressure level in 1 m (indoors)48 dB (A)
Refrigerant / Amount of refrigerantR404A / 2 kg
Maximum heating water flow rate / Pressure drop1,6 m³/h / 11900 Pa
Heat source flow min.2500 m³/h
Dimensions (W x H x D)**750 x 1900 x 680 mm
Weight245 kg
Connection voltage1/N/PE ~230 V, 50 Hz
Starting current with soft starter30 A
Fuse protectionC 20 A
Type of defrostingReverse circulation
Connection heating1 inch

*Heat output according to EN 14511 at A2/W35 (A2 = air intake temperature +2 °C, W35 = heating water outlet temperature +35 °C).

**Please note that additional space is required for pipe connections, operation and maintenance.

Product data sheet with system accessories: Data sheet as PDF Data sheet by e-mail

Installation and operating instruction: Installation and operating instruction as PDF

Operating limits diagram: Operating limits diagram as PDF

Declaration of conformity: Declaration of conformity as PDF