Press Trade Fair Newsletter Sitemap Search:

Dimplex / Products / Heat pumps / Air-to-Water / Outdoor installation

LA 26HS

High-temperature air-to-water heat pump

LA 26HS
LA 26HS

High temperature air-to-water heat pump for outdoor installation with external temperature controlled heat pump manager. Sound-optimised through the use of low-noise crescent wing axial-flow fans and deflector hoods. Energy-efficient defrosting by reverse circulation und diagonally positioned evaporator. Universal design with optional DHW preparation and the option of flexible expansion for:

  • Bivalent or bivalent-renewable operating mode
  • Distribution systems with unmixed and mixed heating circuits
In the summer a maximum heating flow temperature of 58 °C is available for domestic hot water preparation. Integrated flow sensor and soft starter, return flow sensor and external temperature sensor included in the scope of supply. Electric cable EVL ... to connect the heat pump and heat pump manager, must be ordered separately.

Information on leak tests and refrigerant quantities can be found here.

Technical data

High-temperature air-to-water heat pump (High temperature)
Order reference LA 26HS
Casing colourwhite aluminium
max. flow temperature75 °C
Lower operating limit heat source (heating operation) / Upper operating limit heat source (heating operation)-25 to 35 °C
Heat output with 1 compressor / COP A-7/W35*12,9 kW / 2,6
Heat output 1 compressor at A2/W35 / COP A2/W35*15,7 kW / 3
Heat output with 1 compressor / COP A7/W35*19,5 kW / 3,6
Heat output with 1 compressor / COP A10/W35*20,2 kW / 3,7
Nominal consumption according to EN 14511 at A2/W355,16 kW
Sound power level device66 dB (A)
Sound pressure level in 10 m41 dB (A)
Refrigerant / Amount of refrigerantR404A / 3,7 kg
Maximum heating water flow rate / Pressure drop2,7 m³/h / 8200 Pa
Dimensions (W x H x D)**1680 x 1710 x 1000 mm
Weight418 kg
Connection voltage3/N/PE ~400 V, 50 Hz
Starting current with soft starter30 A
Fuse protectionC 25 A
Type of defrostingReverse circulation
Connection heating1 ¼ inch

*Heat output and COP according to EN 14511 at A2/W35 (A2 = air intake temperature +2 °C, W35 = heating water outlet temperature +35 °C)

**Please note that additional space is required for pipe connections, operation and maintenance.

Product data sheet with system accessories: Data sheet as PDF Data sheet by e-mail

Installation and operating instruction: Installation and operating instruction as PDF

Product information: Product information as PDF

Operating limits diagram: Operating limits diagram as PDF

Declaration of conformity: Declaration of conformity as PDF

» Login