Press Trade Fair Newsletter Sitemap Search:

Dimplex / Products / Heat pumps / Air-to-Water / Outdoor installation

LA 26PS

Medium-temperature air-to-water heat pump with two performance levels

LA 26PS
LA 26PS

Medium-temperature air-to-water heat pump for outdoor installation with external temperature controlled WPM 2006 plus heat pump manager and two compressors for flexible capacity. Sound-optimised through the use of noise-reducing crescent wing axial fans and air deflector hoods; energy-efficient hot gas defrosting for optimum operation in combination with radiators. Universal design with optional DHW preparation and the option of flexible expansion for:

  • Bivalent or bivalent-renewable operating mode
  • Distribution systems with unmixed and mixed heating circuits
Integrated flow sensor and soft starter, return flow sensor and external temperature sensor included in the scope of supply. Electric cable EVL ... to connect the heat pump and heat pump manager, must be ordered separately.

Information on leak tests and refrigerant quantities can be found here.

Seal of approval EHPA

European Heat Pump Association - EHPA
 

Technical data

Medium-temperature air-to-water heat pump with two performance levels (Medium temperature)
Order reference LA 26PS
Casing colourwhite aluminium
max. flow temperature65 °C
Lower operating limit heat source (heating operation) / Upper operating limit heat source (heating operation)-25 to 35 °C
Heat output with 1 compressor / COP A-7/W35*8,4 kW / 2,2
Heat output with 2 compressors / COP A-7/W35*13,9 kW / 2,5
Heat output 1 compressor at A2/W35 / COP A2/W35*11,5 kW / 3
Heat output 2 compressors at A2/W35 / COP A2/W35*18,6 kW / 3
Heat output with 1 compressor / COP A7/W35*13,3 kW / 3,5
Heat output with 2 compressors / COP A7/W35*22,9 kW / 3,5
Heat output with 1 compressor / COP A10/W35*14,7 kW / 4
Heat output with 2 compressors / COP A10/W35*25,9 kW / 4
Nominal consumption according to EN 14511 at A2/W356,2 kW
Sound power level device68 dB (A)
Sound pressure level in 10 m41 dB (A)
Refrigerant / Amount of refrigerantR290 / 2,5 kg
Maximum heating water flow rate / Pressure drop3,8 m³/h / 8900 Pa
Heat source flow min.8000 m³/h
Dimensions (W x H x D)**1680 x 1710 x 1000 mm
Weight371 kg
Connection voltage3/N/PE ~400 V, 50 Hz
Starting current with soft starter30 A
Fuse protectionC 25 A
Type of defrostingHot gas
Connection heating1 ¼ inch
Seal of approval EHPA (valid until)Yes / 09.06.2013

*Heat output and COP according to EN 14511 at A2/W35 (A2 = air intake temperature +2 °C, W35 = heating water outlet temperature +35 °C)

**Please note that additional space is required for pipe connections, operation and maintenance.

Product data sheet with system accessories: Data sheet as PDF Data sheet by e-mail

Installation and operating instruction: Installation and operating instruction as PDF

Product information: Product information as PDF

Operating limits diagram: Operating limits diagram as PDF

Declaration of conformity: Declaration of conformity as PDF