Dimplex / Products / Heat pumps / Air-to-Water /
|
LA 26PS |
Medium-temperature air-to-water heat pump for outdoor installation with external temperature controlled WPM 2006 plus heat pump manager and two compressors for flexible capacity. Sound-optimised through the use of noise-reducing crescent wing axial fans and air deflector hoods; energy-efficient hot gas defrosting for optimum operation in combination with radiators. Universal design with optional DHW preparation and the option of flexible expansion for:
Information on leak tests and refrigerant quantities can be found here.
| Medium-temperature air-to-water heat pump with two performance levels (Medium temperature) | ||
|---|---|---|
| Order reference | LA 26PS | |
| Casing colour | white aluminium | |
| max. flow temperature | 65 °C | |
| Lower operating limit heat source (heating operation) / Upper operating limit heat source (heating operation) | -25 to 35 °C | |
| Heat output with 1 compressor / COP A-7/W35* | 8,4 kW / 2,2 | |
| Heat output with 2 compressors / COP A-7/W35* | 13,9 kW / 2,5 | |
| Heat output 1 compressor at A2/W35 / COP A2/W35* | 11,5 kW / 3 | |
| Heat output 2 compressors at A2/W35 / COP A2/W35* | 18,6 kW / 3 | |
| Heat output with 1 compressor / COP A7/W35* | 13,3 kW / 3,5 | |
| Heat output with 2 compressors / COP A7/W35* | 22,9 kW / 3,5 | |
| Heat output with 1 compressor / COP A10/W35* | 14,7 kW / 4 | |
| Heat output with 2 compressors / COP A10/W35* | 25,9 kW / 4 | |
| Nominal consumption according to EN 14511 at A2/W35 | 6,2 kW | |
| Sound power level device | 68 dB (A) | |
| Sound pressure level in 10 m | 41 dB (A) | |
| Refrigerant / Amount of refrigerant | R290 / 2,5 kg | |
| Maximum heating water flow rate / Pressure drop | 3,8 m³/h / 8900 Pa | |
| Heat source flow min. | 8000 m³/h | |
| Dimensions (W x H x D)** | 1680 x 1710 x 1000 mm | |
| Weight | 371 kg | |
| Connection voltage | 3/N/PE ~400 V, 50 Hz | |
| Starting current with soft starter | 30 A | |
| Fuse protection | C 25 A | |
| Type of defrosting | Hot gas | |
| Connection heating | 1 ¼ inch | |
| Seal of approval EHPA (valid until) | Yes / 09.06.2013 | |
*Heat output and COP according to EN 14511 at A2/W35 (A2 = air intake temperature +2 °C, W35 = heating water outlet temperature +35 °C)
**Please note that additional space is required for pipe connections, operation and maintenance.
Product data sheet with system accessories:
as PDF 
by e-mail
Installation and operating instruction:
as PDF
Product information:
as PDF
Operating limits diagram:
as PDF
Declaration of conformity:
as PDF